Refrigerant CO₂e table for F-Gas leak checks
To know whether a system needs a leak check, and how often, you convert the charge to tonnes of CO₂e. This table gives the GWP of 17 common refrigerants and the charge in kilograms at which each reaches the 5, 50 and 500 tonne thresholds under the Great Britain F-Gas regulation, with the sources and the sum.
iPhone: No card. No account. First report free to fill in.In your browser: Free account, no card. First report free to fill in.

The sum
The charge in tonnes of CO₂e is the charge in kilograms multiplied by the refrigerant's GWP, divided by 1,000. For example 3 kg of R32 is 3 × 675 ÷ 1,000 = 2.025 tonnes CO₂e. Compare the exact figure with the thresholds, never a rounded one: 2.39 kg of R410A is 4.99 tonnes, which is under 5 tonnes, and 2.4 kg is 5.01 tonnes, which is over.
What the figure decides
- Under 5 tonnes CO₂e: no periodic leak check under Article 4. Hermetically sealed equipment under 10 tonnes is also exempt if it is labelled as such.
- 5 tonnes to under 50: a leak check at least every 12 months, or every 24 months if a leak detection system is fitted.
- 50 tonnes to under 500: at least every 6 months, or every 12 months with a leak detection system.
- 500 tonnes or more: at least every 3 months, or every 6 months with a leak detection system, and Article 5 requires a leak detection system to be fitted.
Sources: Article 4 and Article 5 of Regulation 517/2014 as it applies in Great Britain, and GOV.UK on checking F gas equipment for leaks, checked 11 November 2026. See also the F-Gas leak check frequency guide.
GWP values and the CO₂e thresholds
The table shows each gas's GWP and the charge at which each threshold is reached. The values are the AR4 figures used by the Great Britain regulation: Annex I and II of the regulation give single gases such as R32 (675), R134a (1,430), R1234yf (4) and R1234ze (7), and Annex IV says the GWP of a blend is the weighted average of its components. R410A, R407C, R404A and R452A match the figures GOV.UK publishes. For R448A, GOV.UK lists 1,386 and the Annex IV weighted average works out at 1,387, which is the figure used here. Blend compositions are from ASHRAE 34.
| Refrigerant | GWP (AR4) | 5 t CO₂e reached at (kg) | 50 t reached at (kg) | 500 t reached at (kg) | Basis |
|---|---|---|---|---|---|
| R32 | 675 | 7.41 | 74.08 | 740.75 | Annex I |
| R134a | 1,430 | 3.50 | 34.97 | 349.66 | Annex I |
| R410A | 2,088 | 2.40 | 23.95 | 239.47 | Annex IV blend |
| R407C | 1,774 | 2.82 | 28.19 | 281.85 | Annex IV blend |
| R404A | 3,922 | 1.28 | 12.75 | 127.49 | Annex IV blend |
| R407A | 2,107 | 2.38 | 23.74 | 237.31 | Annex IV blend |
| R407F | 1,825 | 2.74 | 27.40 | 273.98 | Annex IV blend |
| R448A | 1,387 | 3.61 | 36.05 | 360.50 | Annex IV blend |
| R449A | 1,397 | 3.58 | 35.80 | 357.91 | Annex IV blend |
| R452A | 2,140 | 2.34 | 23.37 | 233.65 | Annex IV blend |
| R454B | 466 | 10.73 | 107.30 | 1,072.97 | Annex IV blend |
| R454C | 148 | 33.79 | 337.84 | 3,378.38 | Annex IV blend |
| R513A | 631 | 7.93 | 79.24 | 792.40 | Annex IV blend |
| R507A | 3,985 | 1.26 | 12.55 | 125.48 | Annex IV blend |
| R422D | 2,729 | 1.84 | 18.33 | 183.22 | Annex IV blend |
| R427A | 2,138 | 2.34 | 23.39 | 233.87 | Annex IV blend |
| R23 | 14,800 | 0.34 | 3.38 | 33.79 | Annex I |
Charge in kilograms at which the threshold is reached, rounded up to two decimal places: that charge or more is at or above the threshold. Values checked 11 November 2026.
Gases that carry no leak-check duty
- R1234yf (GWP 4) and R1234ze (GWP 7) are Annex II gases: subject to reporting, but not to the Article 4 leak-check duty.
- R290 (propane), R600a (isobutane), R717 (ammonia) and R744 (CO₂) are not fluorinated greenhouse gases, so Article 4 does not apply to them.
Safety rules for flammable and toxic refrigerants are a separate matter and still apply.
How Maintivo uses the table
On the Split AC/VRF leak check and the Chiller service forms you choose the refrigerant from a list of more than 20 gases and enter the charge in kilograms. Maintivo works out the exact tonnes of CO₂e, sets the leak-check band, says whether a leak detection system is required and writes the next leak check due against the unit in the equipment register. It follows the same figures as this page. See the F-Gas leak check app.
This table is a guide. Check the figure against the cylinder label and the guidance of your certification body for the job in front of you. Maintivo produces and stores the record; the engineer remains the competent person who signs it.
Questions about refrigerant CO2e
Multiply the charge in kilograms by the refrigerant's GWP and divide by 1,000 to get tonnes of CO2 equivalent. For example 3 kg of R32 (GWP 675) is 2.025 tonnes CO2e. Compare the exact figure with the 5, 50 and 500 tonne thresholds.
R32 is 675 and R410A is 2,088, on the AR4 basis used by the Great Britain F-Gas regulation. R410A is a blend, so its figure comes from the weighted average of its components under Annex IV of the regulation, and GOV.UK publishes the same number.
A leak check is required from 5 tonnes CO2e. For R410A that is 2.4 kg (5,000 ÷ 2,088 = 2.395 kg), so 2.39 kg is under the threshold and 2.4 kg or more is over it. Hermetically sealed equipment under 10 tonnes is exempt if it is labelled as hermetically sealed.
Every 12 months from 5 tonnes CO2e, every 6 months from 50 tonnes and every 3 months from 500 tonnes. A leak detection system doubles each period, to 24, 12 and 6 months. Article 5 requires a leak detection system from 500 tonnes.
No. R290 (propane) and R744 (CO2) are not fluorinated greenhouse gases, so the Article 4 leak-check duty does not apply. R1234yf and R1234ze are Annex II gases, subject to reporting but not to the Article 4 leak-check duty.