How to work out the F-Gas leak check interval

Multiply the refrigerant charge in kilograms by the gas's Global Warming Potential (GWP) to get kilograms of CO₂e, divide by 1,000 for tonnes, then read the interval off the 5, 50 and 500 tonne bands. Under 5 tonnes there is no mandatory check; 5 tonnes and over is every 12 months; 50 and over every 6 months; 500 and over every 3 months. A fixed leak detection system doubles each interval.