How to work out the F-Gas leak check interval

Multiply the refrigerant charge in kilograms by the gas's Global Warming Potential (GWP) to get kilograms of CO₂e, divide by 1,000 for tonnes, then read the interval off the 5, 50 and 500 tonne bands. Under 5 tonnes there is no mandatory check; 5 tonnes and over is every 12 months; 50 and over every 6 months; 500 and over every 3 months. A fixed leak detection system doubles each interval.

Page 1 of a sample Maintivo F-Gas Leak Check Record: company letterhead, client and site, equipment details, refrigerant R410A at 8.4 kg shown as 17.5 tonnes CO2e, and the next leak check due on 28 September 2027.
Sample report: fictional customer and data. See the full sample report (PDF)
The report

The sum, printed on a real record

An F-Gas leak check record produced by Maintivo from a sample visit: 8.4 kg of R410A is 17.5 tonnes CO₂e, which is in the 5 to 50 tonne band, so the next check is due in 12 months.

See the full sample report (PDF)